Custom Cable Corp. - NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
Search Catalog
By Item #
By Keyword
All Categories
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
Specify Custom Cable Corporation . . . a name that has become synonymous with performance and reliability.
All Categories
>
Plenum Cable
>
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
>
View Items
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
Check up to five results to perform an action.
larger image
Applications
Inside/Outside fire and burglar alarm systems
Smoke detection system
Voice and digital communications systems
Features
Installation in air plenums without the use of conduit
Passes Steiner Tunnel Low Smoke and Flame Test
Outstanding oil and moisture resistance
Excellent electrical and mechanical properties
Printable Page
Email This Page
Save To Favorites
Results per Page :
25
50
100
200
Results 1 - 15 of 15
1
Item #
Item Name
Size (AWG/MCM)
No. of Conductors
Strands
Nominal Insulation Thicknes (inches)
Nominal Jacket
Thickness (inches)
Nominal O.D (inches)
Nominal Weight
(LBS/MFT)
11250S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
20
2
Solid
0.007
0.010
0.116
19
11251S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
20
4
Solid
0.007
0.010
0.135
27
11252S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
20
6
Solid
0.007
0.010
0.162
36
11260S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
18
2
Solid
0.010
0.015
0.158
26
11261S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
18
4
Solid
0.010
0.015
0.183
40
11262S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
18
6
Solid
0.010
0.015
0.204
54
11270S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
16
2
Solid
0.010
0.015
0.180
36
11271S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
16
4
Solid
0.010
0.015
0.210
56
11272S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
16
6
Solid
0.010
0.015
0.237
77
11280S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
14
2
Solid
0.012
0.015
0.218
53
11281S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
14
4
Solid
0.012
0.015
0.248
85
11282S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
14
6
Solid
0.012
0.015
0.298
119
11290S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
12
2
Solid
0.012
0.015
0.252
78
11291S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
12
4
Solid
0.012
0.015
0.283
127
11292S
NEC Article 760-2(b)- Type FPLP Multi Conductor Foil Shielded Plenum Cable
12
6
Solid
0.012
0.015
0.349
176
Results 1 - 15 of 15